Capacity:10 kVA | 15 kVA | 20 kVA | 30 kVA | 40 KVA | 60 KVA | 80 kVA | 100 kVA | 120 kVA
INPUT:
Input wirting:Three-phase five-wire (30+N+PE)
Rated voltage: 380/400/415 Vac
Voltage range: 285-475 V
Frequency range: (50/60) ± 5 Hz
Power factor: 0.95 (with Filter)
Delayed start of rectifier:10 s (1-300 settable)
Bypass voltage range: ±20% (settable)
OUTPUT:
Output wiring: Three-phase five-wire (30+ N + PE)
Rated voltage: 380/400/415 Vac
Output Voltage regulation: ±1%
Output Frequency: 50/60 Hz ± 0.1% Hz in battery mode
Waveform: Sinusoidal
Power factor: 0.9/0.8
Voltage distortion (THDv): 1% (linear load); 5% (non-linear load)
Crest Factor: 3:1
Overload: 105%~110% for 60 min, 110% 125% for 10 min
BATTERIES:
DC Voltage: Lead acid battery: 360 Vdc Lithium iron phosphate battery: 384 Vdc
Number of battery: Lead Acid battery: 12 V x 30 pcs (support 28-32 pcs) Lead Acid battery: 2 V x 180 pcs (support 168-192 pcs) Lithium iron phosphate battery: 3.2 V x 120 pcs (support 112/120 pcs)
Charging current: Charging rate (settable) x battery capacity (settable) x number of battery groups (settable)
SYSTEM:
Efficiency: In Line mode: Max, 93%; ECO mode: 98%
Max. number of parallel connections: 6
Protections: Short-circuit, overload, over temperature, battery low voltage, over voltage, under voltage and fan failure